Titus SteriTec/LineaTec IOM User Manual

Browse online or download User Manual for Equipment Titus SteriTec/LineaTec IOM. Titus SteriTec/LineaTec IOM User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 2
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
INSTALLATION
INSTRUCTIONS
D-CED-IM 4-04-01
(Please see reverse side.)
INSTALLATION PROCEDURE
Prior to Installation:
1. Identify all parts for each individual system: straight sections,
corner transitions, slot diffusers, and joiner mullions.
2. Determine quantity of bolts, nuts, washers and clear silicone
sealer required to join sections together, as TITUS does not
provide.
1
/4” diameter bolts are recommended.
3. Layout sections on the floor to check fit-up before mounting into
ceiling.
Installation:
The LineaTec or SteriTec can be installed as a surface mount or as a T-
Bar lay-in. Either method of installation will require support from above.
One piece construction LineaTec:
4. Surface Mounted: Hang by wire or rods using the four hanger
brackets located on top of the plenum (see Detail 5).
5. T-Bar Lay-In: Use same support method as surface mount.
Multi-Piece Construction LineaTec or SteriTec:
These units are fabricated in multiple pieces and assembled as
follows:
6. Each plenum section is to be hung by either wire or rods utilizing
the four hanger brackets located on top of each plenum. Faces
(slot diffusers) or corner transition face panels will need to be
removed during this procedure. Be sure to re-install the face into
the same plemum it was removed from.
7. As each plenum section is hung and before bolting to the
adjoining plenum, install the alignment strips (aluminum
units
only) and apply a clear silicone sealer to one of the mating
flanges as shown in Detail 3. Remove any excess sealer from
inside the plenum after bolting. Check alignment and fitting of
plenum sections during assembly.
8. Repeat steps 6 and 7 for each additional plenum section or
corner transition.
9. After assembly of all plenum sections and corner transitions has
been completed, re-check fit-up and alignment.
10. Re-install the face (slot diffusers) and corner transition face
panels (Detail 1) along with joiner mullions (Detail 2).
Optional 1-Slot Blank-Off:
11. The LineaTec and SteriTec will always have 2-slots. When only
1-slot is required, an option a blank-off for one of the slots is
provided. This option can be added at the time of fabrication or
later at the jobsite.
12. The blank-off along with the perforated screen is held in place
by U-shaped clips as shown in Detail 4. To remove or add the
blank-off at the jobsite simply remove the face (slot diffuser) only
shown in Detail 1. Once the face has been removed, remove the
U-shaped clips along the side where blank-off is to be added or
removed. Then either add or remove the blank-off and re-install
the U-shaped clips.
DETAIL 1 DETAIL 2
SteriTec and LineaTec - Critical Environment Diffusers
Page view 0
1 2

Summary of Contents

Page 1 - INSTRUCTIONS

INSTALLATION INSTRUCTIONS D-CED-IM 4-04-01(Please see reverse side.)INSTALLATION PROCEDUREPrior to Installation:1. Identify all parts for each

Page 2 - DETAIL 4DETAIL 3

Part # 000000-00DETAIL 5DETAIL 4DETAIL 3605 Shiloh Road • Plano, Texas 75074 • 972- 212- 4800Note: This submittal is meant to demonstrate general dime

Comments to this Manuals

No comments